Page 196 Chapter 10: Troubleshooting
023 - FM - Multiple Pump Assignment
Figure 164: Warning 023-FM Multiple Pump
This warning appears at the submaster whenever the Flow Max
feature has been incorrectly set up by the user. Using Flow Max,
it is possible to assign a device (in this case the Pump) to any of
the Flow Max participants. If the Pump is assigned to more than
one controller, this warning will appear at the submaster.
Devices must be installed at one physical location (satellite)
only.
Action:
Step 1 Review the Flow Max device connection list at the
submaster via the F4=REVIEW ALL selection.
Look for two or more occurrences of the Pump
throughout the Flow Max participants.
Step 2 Note the incorrect assignment and remove it from
the location(s) which are in error.
Example:
Assume the pump's physical connection is at the
submaster (address 01-00) and the pump was
inadvertent assigned to the participant at address
01-03.
To correct this assignment, go to satellite
address 01-03 (fourth controller on the hardwire
link) and delete the entry using the Flow Max
setup function.
WARNING = MULTIPLE PUMP 06/14/96 11:30PM