Rain Master Irrigation Systems DX2 User Manual
Page 176 Chapter 10: Troubleshooting
006 - Controller Main Line Break Occurred
Figure 147: Warning 006-Main Flow
The maximum main line break flow rate was exceeded for the
controller. The warning lists the station number (7) which was
on at the time the controller Main Line Limit failure occurred as
well as the measured flow in GPM (220). All irrigation for the
controller is immediately terminated. In addition, the Normally
Open Master Valve terminal (N.O.) is energized with 24 VAC.
Any and all future automatic irrigation will not occur until this
warning is cleared from the controller.
Action:
Step 1 Inspect the main line as well as major branches for
failure.
Step 2 Inspect the station(s) which were operating at the
time of the failure.
Step 3 Turn on the station by using the Manual Test
function, and observe the flow in GPM.
Step 4 Compare the measured flow rate with the station
limits as well as the controller Main Line Limit and
verify proper operation. The Main Line Limit
should be larger than the total of all simultaneously
"On" stations.
Step 5 Upon resolution of problem, CLEAR all warnings at
the controller.
WARNING = MAIN FLOW
MV
06/20/96 10:46PM
STA=7, MV1 GPM=220 |¾||½|